Industrial Air Cooled Chiller Model LTC
Air Cooled Chiller -Box Type Chiller -Air to Water Chiller -CE Certificate Chiller -High Efficiency Chiller
Box Type Industrial Air Cooled Chiller Model LTC
LTC Series Box Type Industrial Air Cooled Water Chiller
Two Kinds of Models:Air Cooled Water Chiller/Air to Water Chiller
1. Cooling Condition: Chilled Water In/Out 12°C/7°C;Cooling Water In/Out 30°C/35°C
Models: LT03AS-40AD
Cooling Capacity: 8KW-120KW
2.Cooling Condition: Chilled Glycol in/out -1/-5°C;Cooling Water In/Out 30°C/35°C
Models: LT03ASL-40ADL
Cooling Capacity: 4.7KW-61.6KW
INTRODUCTION:
1)With scroll, or recipocating compressor of high quality, high efficient heat exchangers, excellent system design, by excllent
process, the chillers is of suffient capacity and efficiency.
2)The chillers will work stably for long time period as they are produced by excllent process, composed of reliable control
components and professional control procedure.
3)Complete safety protection:
1.High&low pressure protection, pressure safety value protection;
2.Overload protection to the compressor;
3.Power supply protect for phase lack, counter phase, voltage too high and voltage deficient;
4.Water system protection for freezing breaking, water lack etc.
Air Cooled Chiller Diagram:
FEATURE
1.Ready to work only after connected to chilled water system;
2.A stainless steel water vessel,a low noise pump have been fixed inside the chiller;
3.The chillers of capacity below 50KW is movable by wheels with them;
4.The chillers of capacity over 50KW are double refrigeration system design that is good to reduce the frequent start and stop for load change. The chillers can run even 1 system is in trouble.
5.Strict test and inspection has been made before the chillers are delivered.
Details As Follows:
MODEL LT- | 03AS | 05AS | 08AS | 10AS | 12AS | 15AS | 20AD | 25AD | 30AD | 40AD | |
CoolingCapacity | KW | 8.3 | 13.7 | 22.1 | 29.5 | 34 | 44.1 | 59 | 68 | 88.2 | 120 |
103kcal/hr | 7.1 | 11.8 | 19 | 25.4 | 29.2 | 37.9 | 50.7 | 58.5 | 75.9 | 103.2 | |
Power(kW) | 3.1 | 5 | 7.4 | 9.7 | 11.9 | 15.3 | 19.4 | 23.7 | 30.6 | 40.5 | |
Current(A) | 5.7 | 9.7 | 14.3 | 18.2 | 22.1 | 28.8 | 36.3 | 44.1 | 57.6 | 64.2 | |
Compressor | Quty(PCS) | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 |
Power(kW) | 2.55 | 3.96 | 6.11 | 8.06 | 9.9 | 12.39 | 16.1 | 19.8 | 24.8 | 34.1 | |
Current(A) | 4.39 | 7.69 | 11.41 | 14.86 | 18.25 | 22.7 | 29.7 | 36.5 | 45.4 | 49.6 | |
Refrigerant | Type | R22 | |||||||||
Control | Thermal expension valve | ||||||||||
Fan | Power(KW) | 0.2 | 0.45 | 0.5 | 0.9 | 1.2 | 1.4 | 1.7 | 2.2 | 3.12 | 4.2 |
Current(A) | 0.6 | 0.9 | 1.4 | 1.8 | 2.3 | 2.9 | 5.4 | 7.6 | 9.6 | 10 | |
Water Pump | Type | Centrifugal pump | |||||||||
Power(KW) | 0.37 | 0.55 | 0.75 | 0.75 | 0.75 | 1.5 | 1.5 | 1.5 | 2.2 | 2.2 | |
Current(A) | 0.75 | 1.1 | 1.5 | 1.5 | 1.5 | 3.2 | 3.2 | 3.2 | 4.6 | 4.6 | |
Pressure Head(mHo2) | 15 | 20 | 22 | 20 | 17 | 25 | 24 | 18 | 22 | 22 | |
Condenser | Type | Copper tupe and al fin | |||||||||
Evaporator | water pipe connection(mm) | DN25 | DN40 | DN50 | DN65 | ||||||
Water flow(L/min) | 23.7 | 39.3 | 63.4 | 84.6 | 97.5 | 126.4 | 169.1 | 194.9 | 252.8 | 344 | |
Water Tank | Volume(L) | 65 | 75 | 140 | 140 | 150 | 250 | 325 | 325 | 370 | 400 |
Fill,discharge,overflow port | DN20 | ||||||||||
Overall Size | Length mm | 1060 | 1060 | 1520 | 1620 | 1720 | 1810 | 2020 | 2270 | 2470 | 2670 |
Width mm | 740 | 740 | 850 | 850 | 850 | 930 | 1010 | 1150 | 1150 | 1240 | |
Hight mm | 1340 | 1450 | 1550 | 1600 | 1600 | 1730 | 1930 | 1930 | 2080 | 2220 | |
Weight | KG | 220 | 236 | 320 | 372 | 435 | 610 | 750 | 850 | 950 | 1050 |
Remark:1.Colling Condition:Chilled water in/out 12/7°C;Ambient Temperature 35°C; | |||||||||||
2.Suitable chilled water temperature:9-25°C; | |||||||||||
3.Power supply: 3P-380V-50HZ;with voltage allowance ±10%,voltage dif between the phase lines±2%; | |||||||||||
4.The data above is for R22, contact us if that for R134a,R407c and other refrigerant need; | |||||||||||
5.There may be Changes for improvement without notice, confirm always before your order. |
Industrial Air Cooled Chiller Model LTC